TITANUS TOP·SENS®
TITANUS® FUSION
The TITANUS TOP·SENS® is an air sampling smoke detector with all the bells and whistles. It has all the features of the PRO·SENS®, plus a
network card slot to allow network capability via Ethernet / SNMP connection. This premium product includes a bar graph to display smoke density
levels in the event of fire.
Thanks to a combination of highly sensitive HPLS optical technology and LOGIC.SENS fire pattern recognition, the TITANUS TOP∙SENS®
combines maximum sensitivity and maximum security against false alarms in rooms as large as 5,760 m². A second detector module can be used to
create a dual detector dependency setup, or to monitor a second area independently. Each detector module can be configured with up to three
alarm levels. An additional connection socket makes parallel display possible.
Advantages
•
The TITANUS TOP·SENS® features a graded alarm-activation concept with up to three alarms per detector module.
•
Smoke levels can optionally be displayed on the unit as a bar graph.
•
The pipe network can be configured with up to 1 x 100 or 2 x 72 air sampling points.
•
An extensive range of DIN EN 54-20 certified accessories allow operators to tailor their systems to their individual
needs.
•
The system’s modular design makes it a customisable and cost-effective solution.
•
Versions for noise-critical areas (23 dB (A) and up) or cold storage (as low as -40 °C) are available as well.
•
TITANUS®PipeXpress Secure project planning and configuration is just five mouse clicks away.
•
The plug-and-play design saves time on commissioning.
WAGNER’s newest air sampling smoke detector, the TITANUS®FUSION, is an affordable high-end air sampling smoke detector that combines
decades of experience in early fire detection with innovative engineering. The smoke detection system offers a great deal of planning flexibility: it can
reliably monitor a wide range of areas of up to 3,200 m² in size, and can detect even the tiniest quantities of smoke particles early on.
Advantages
•
Highly sensitive, false alarm-proof smoke detection for mid-sized areas
•
High Power Light Source technology allows normal to extremely high sensitivity
•
Maximum security against false alarms thanks to LOGIC·SENS
•
PIPE·GUARD patented air flow monitoring
•
Detector module with response sensitivity of up to 0.015 % obs./m, 0.1 % obs./m or 0.5 % obs./m
•
Monitors areas up to 3,200 m² in size; max. pipe length of 2 x 160 m with up to 2 x 20 air sampling points
•
Precise air flow monitoring within measuring chamber ensures maximum operational reliability
•
Low operating costs thanks to extremely low power consumption (as low as 140 mA, depending on device type)
•
Optional alarm system with adjustable pre-alarm
•
Plug-and-play system for easy planning and installation
•
Range of DIN EN 54-20/ISO 7240-20 certified accessories
•
Operating temperature range: -30 °C to +60 °C (SILENT version: 0 °C to +40 °C)
•
Usable in very dusty environments thanks to (optional) filter concept
•
SILENT version (23 dB(A) and up) for noise-critical areas
The universal TITANUS PRO∙SENS® is WAGNER’s best-selling air sampling smoke detector. Depending on the situation, the one or two detector
modules (each with a one-stage alarm) can be set to sensitivity levels as high as 0.015 % obs./m on their primary alarms. The highly modular air
sampling smoke detection system offers solutions for both simple and highly specialised areas of application.
WAGNER’s TITANUS PRO∙SENS® air sampling smoke detector is designed to monitor large areas of up to 5,760 m². Thanks to a combination of
innovative High Power Light Source (HPLS) technology and patented LOGIC∙SENS fire pattern recognition, the TITANUS PRO∙SENS® provides
maximum sensitivity and security against false alarms even in difficult environmental conditions.
Advantages
•
The TITANUS PRO·SENS® monitors rooms and equipment using two detector modules in a dual-detector
dependency configuration.
•
Additional alarm indicators can be connected as desired.
•
The number of air sampling points can be freely adapted to individual circumstances (up to 1 x 100 or 2 x 72 points).
•
A range of DIN EN 54-20 certified accessories provides even greater modularity, thus making the TITANUS
PRO·SENS® air sampling smoke detector an even more cost-effective option.
•
It is available in Standard, SILENT (23 dB (A) and up, for noise-critical areas) and Cold Storage (for temperatures as
low as -40 °C) versions—a specific fire protection solution for any area of application.
•
TITANUS®PipeXpress Project planning and configuration is fast and secure.
•
The plug-and-play system makes commissioning quick and easy.