TITANUS TOP·SENS®
 
 
 
  TITANUS® FUSION
 
 
  
 
 
  
 
 
  The TITANUS TOP·SENS® is an air sampling smoke detector with all the bells and whistles. It has all the features of the PRO·SENS®, plus a 
  network card slot to allow network capability via Ethernet / SNMP connection. This premium product includes a bar graph to display smoke density 
  levels in the event of fire.
  Thanks to a combination of highly sensitive HPLS optical technology and LOGIC.SENS fire pattern recognition, the TITANUS TOP∙SENS® 
  combines maximum sensitivity and maximum security against false alarms in rooms as large as 5,760 m². A second detector module can be used to 
  create a dual detector dependency setup, or to monitor a second area independently. Each detector module can be configured with up to three 
  alarm levels. An additional connection socket makes parallel display possible.
  Advantages
  •
  The TITANUS TOP·SENS® features a graded alarm-activation concept with up to three alarms per detector module.
  •
  Smoke levels can optionally be displayed on the unit as a bar graph.
  •
  The pipe network can be configured with up to 1 x 100 or 2 x 72 air sampling points.
  •
  An extensive range of DIN EN 54-20 certified accessories allow operators to tailor their systems to their individual 
  needs.
  •
  The system’s modular design makes it a customisable and cost-effective solution.
  •
  Versions for noise-critical areas (23 dB (A) and up) or cold storage (as low as -40 °C) are available as well.
  •
  TITANUS®PipeXpress Secure project planning and configuration is just five mouse clicks away.
  •
  The plug-and-play design saves time on commissioning.
 
 
  WAGNER’s newest air sampling smoke detector, the TITANUS®FUSION, is an affordable high-end air sampling smoke detector that combines 
  decades of experience in early fire detection with innovative engineering. The smoke detection system offers a great deal of planning flexibility: it can 
  reliably monitor a wide range of areas of up to 3,200 m² in size, and can detect even the tiniest quantities of smoke particles early on.
  Advantages
  •
  Highly sensitive, false alarm-proof smoke detection for mid-sized areas
  •
  High Power Light Source technology allows normal to extremely high sensitivity
  •
  Maximum security against false alarms thanks to LOGIC·SENS
  •
  PIPE·GUARD patented air flow monitoring
  •
  Detector module with response sensitivity of up to  0.015 % obs./m, 0.1 % obs./m or 0.5 % obs./m
  •
  Monitors areas up to 3,200 m² in size; max. pipe length of 2 x 160 m with up to 2 x 20 air sampling points
  •
  Precise air flow monitoring within measuring chamber ensures maximum operational reliability
  •
  Low operating costs thanks to extremely low power consumption (as low as 140 mA, depending on device type)
  •
  Optional alarm system with adjustable pre-alarm
  •
  Plug-and-play system for easy planning and installation
  •
  Range of DIN EN 54-20/ISO 7240-20 certified accessories
  •
  Operating temperature range: -30 °C to +60 °C (SILENT version: 0 °C to +40 °C)
  •
  Usable in very dusty environments thanks to (optional) filter concept
  •
  SILENT version (23 dB(A) and up) for noise-critical areas
 
 
  The universal TITANUS PRO∙SENS® is WAGNER’s best-selling air sampling smoke detector. Depending on the situation, the one or two detector 
  modules (each with a one-stage alarm) can be set to sensitivity levels as high as 0.015 % obs./m on their primary alarms. The highly modular air 
  sampling smoke detection system offers solutions for both simple and highly specialised areas of application.
  WAGNER’s TITANUS PRO∙SENS® air sampling smoke detector is designed to monitor large areas of up to 5,760 m². Thanks to a combination of 
  innovative High Power Light Source (HPLS) technology and patented LOGIC∙SENS fire pattern recognition, the TITANUS PRO∙SENS® provides 
  maximum sensitivity and security against false alarms even in difficult environmental conditions.
  Advantages
  •
  The TITANUS PRO·SENS® monitors rooms and equipment using two detector modules in a dual-detector 
  dependency configuration.
  •
  Additional alarm indicators can be connected as desired.
  •
  The number of air sampling points can be freely adapted to individual circumstances (up to 1 x 100 or 2 x 72 points).
  •
  A range of DIN EN 54-20 certified accessories provides even greater modularity, thus making the TITANUS 
  PRO·SENS® air sampling smoke detector an even more cost-effective option.
  •
  It is available in Standard, SILENT (23 dB (A) and up, for noise-critical areas) and Cold Storage (for temperatures as 
  low as -40 °C) versions—a specific fire protection solution for any area of application.
  •
  TITANUS®PipeXpress Project planning and configuration is fast and secure.
  •
  The plug-and-play system makes commissioning quick and easy.